Factories Act |
Factories (Examination and Test of Pressure Vessels) (Exemption) Order |
O 5 |
G.N. No. S 447/1989 |
REVISED EDITION 1990 |
(25th March 1992) |
[1st December 1989] |
Citation |
1. This Order may be cited as the Factories (Examination and Test of Pressure Vessels) (Exemption) Order. |
Steam boilers |
2. Steam boilers with a maximum permissible working pressure not exceeding 0.5 bar are exempted from section 36(8) to (15) of the Act. |
Steam receiver |
3. Where the safe working pressure of a steam receiver does not exceed 0.5 bar or the product of its safe working pressure and volume does not exceed 100 bar-litre, it shall be exempted from section 37(4) to (8) of the Act. |
Air receiver |
4. Where the safe working pressure of an air receiver does not exceed 0.5 bar or the product of its safe working pressure and volume does not exceed 100 bar-litre, it shall be exempted from section 39(4) to (8) of the Act. |
Refrigerating plant pressure receiver |
5. Where the safe working pressure of a refrigerating plant pressure receiver does not exceed 0.5 bar or the product of its safe working pressure and volume does not exceed 100 bar-litre, it shall be exempted from section 40 of the Act. |