4. In the principal Regulations, in the First Schedule —(a) | in paragraph 1, after the definition of “casement or window type air‑conditioner”, insert —“ “chilled”, in relation to a commercial storage refrigerator, means that the storage temperature of foodstuffs in the refrigerator is continuously maintained at a temperature at or above –1°C and at or below 5°C;”; |
|
| (b) | in paragraph 1, after the definition of “Coefficient of Performance” or “COP”, insert —“ “commercial storage refrigerator” has the meaning given by Part 2 of the Fourth Schedule to the Energy Conservation (Prescribed Regulated Goods) Order 2017;”; |
|
| (c) | in paragraph 1, after the definition of “compact fluorescent lamp without integrated ballast” or “CFLni”, insert —“ “counter”, in relation to a commercial storage refrigerator, means that the refrigerator is lower than 1,050 mm in height with one or more doors or drawers accessing the same compartment;”; |
|
| (d) | in paragraph 1, after the definition of “Energy Consumption” or “EC”, insert —“ “Energy Efficiency Index” or “EEI”, in relation to a commercial storage refrigerator, means the number determined in accordance with the following formula: |
“frozen”, in relation to a commercial storage refrigerator, means that the storage temperature of foodstuffs in the refrigerator is continuously maintained at a temperature at or below –15°C;”; |
|
| (e) | in paragraph 1, after the definition of “N”, insert —“ “net volume”, in relation to a commercial storage refrigerator, means the volume containing foodstuffs within the load limit of the refrigerator;”; |
|
| (f) | in paragraph 1, after the definition of “split type (non‑inverter) air‑conditioner”, insert —“ “SS” means the Singapore Standards; |
“Standard Annual Energy Consumption” or “SAEC” means the standard annual energy consumption in kWh/year determined in accordance with the following formula:(a) | Vn is the net volume, which is the sum of the net volumes of all compartments of the refrigerator, expressed in litres; | (b) | if the refrigerator is a vertical chilled type refrigerator — A is 1.643 and B is 609; | (c) | if the refrigerator is a vertical frozen type refrigerator — A is 4.928 and B is 1472; | (d) | if the refrigerator is a counter chilled type refrigerator — A is 2.555 and B is 1790; and | (e) | if the refrigerator is a counter frozen type refrigerator — A is 5.840 and B is 2380;”; |
|
|
| (g) | in paragraph 1, after the definition of “tungsten halogen lamp”, insert —“ “Uniform Energy Factor” or “UEF”, in relation to a water heater, means the measure of the overall efficiency of the water heater, as specified in the test report; |
“vertical”, in relation to a commercial storage refrigerator, means that the refrigerator is equal to or higher than 1,050 mm in height with one or more doors or drawers accessing the same compartment; |
“water heater” has the meaning given by Part 2 of the Eighth Schedule to the Energy Conservation (Prescribed Regulated Goods) Order 2017;”; |
|
| (h) | in paragraph 2, in item 2, in the second column, replace “4.04” with “4.86 and standby power ≤ 18”; | (i) | in paragraph 2, in item 3, in the second column, replace “4.04” with “5.50 and standby power ≤ 7 × N”; | (j) | in paragraph 2, in item 4, in the second column, replace “4.04 and COP ≥ 3.34” with “4.86 and standby power ≤ 18”; | (k) | in paragraph 2, in item 5, in the second column, replace “4.04 and COP ≥ 3.34” with “5.50 and standby power ≤ 7 × N”; | (l) | in paragraph 2, in item 6, in the second column, replace “0.461” with “0.332”; | (m) | in paragraph 2, in item 7, in the second column, replace “0.427” with “0.312”; | (n) | in paragraph 2, in item 9, in the second column, replace “0.409” with “0.298”; | (o) | in paragraph 2, after item 9, insert — | “9A. | Commercial storage refrigerator |
|
| | |
|
| (p) | in paragraph 2, after item 18, insert — | “19. | Television with resolution of 33,177,600 pixels |
|
| | P ≤ 0.42 × (20 + 4.3224 × screen area) and passive standby power ≤ 0.50W”; |
|
|
| (q) | in paragraph 2, after item 19 (as inserted by paragraph (p)), insert — | (r) | in paragraph 3(d) and (e), delete “and COP ≥ 3.34”; | (s) | in paragraph 3(d) and (e), delete “, COP ≥ 3.78”; | (t) | in paragraph 3(d) and (e), delete “, COP ≥ 4.29”; | (u) | in paragraph 3(d) and (e), delete “, COP ≥ 4.86”; | (v) | in paragraph 3(f), after “refrigerators”, insert “(other than commercial storage refrigerators)”; | (w) | in paragraph 3, after sub‑paragraph (f), insert —“(fa) | for commercial storage refrigerators — | | Energy Efficiency Index (EEI) |
| | | | | | | | | | | | | | | |
”; |
|
|
| (x) | in paragraph 3, after sub‑paragraph (i), insert —“(j) | for water heaters — | | Uniform Energy Factor (UEF) |
| | | | | | | | | | | | | | | |
”; |
|
|
| (y) | in paragraph 4(d), after “refrigerators”, insert “(other than commercial storage refrigerators)”; | (z) | in paragraph 4, after sub‑paragraph (d), insert —“(da) | commercial storage refrigerators: ”; |
|
|
| (za) | in paragraph 4, after sub‑paragraph (e), insert —“(f) | water heaters: ”; and |
|
|
| (zb) | replace paragraph 5 with —5. Subject to regulation 2(2), a test report for any regulated goods must contain the results of tests carried out for the regulated goods in accordance with the applicable test standard or method, as follows: | | | Applicable test standard or method |
| | | | | | (ii) | Split type (inverter) with more than one indoor unit |
|
| | The cooling tests must be conducted at 2 points, namely, the full‑load cooling capacity and the part‑load cooling capacity |
| | (iii) | Split type (inverter) with one indoor unit |
|
| | The cooling tests must be conducted at 2 points, namely, the full‑load cooling capacity and the part‑load cooling capacity |
| | (iv) | Split type (non‑inverter) with more than one indoor unit |
|
| | | | (v) | Split type (non‑inverter) with one indoor unit |
|
| | | | (vi) | Three‑phase variable refrigerant flow (VRF) air‑conditioner |
|
| | The cooling tests must be conducted at 4 points, namely, the full‑load cooling capacity and part‑load cooling capacity at 75%, 50% and 25%. The tests must include a single outdoor unit that services the network of indoor units |
| | | | | | (viii) | Air-conditioners described in items (i) to (vi) (for standby power) |
|
| | | | | | The test must be conducted on cotton textiles using the dry cotton drying programme |
| | | | The luminous flux measurement test must be conducted in accordance with CIE 084‑1989 |
The test conditions for the luminous flux measurement test are as specified in — |
(a) | for tungsten filament lamps, IEC60064:1993+ AMD1:2000+ AMD2:2002+ AMD3:2005; and |
|
(b) | for tungsten halogen lamps, IEC60064:1993+ AMD1:2000+ AMD2:2002+ AMD3:2005 or IEC 60357:2002 |
|
| | | | | | | | IEC 62612:2013 or IEC 62612:2013+ AMD:2015 or IEC 62612:2013+ AMD1:2015+ AMD2:2018 |
The luminous flux measurement test must be conducted in accordance with CIE S 025:2015 |
| | | | IEC 60901:1996+ AMD1:1997+ AMD2:2000 |
| | | | | | (vi) | LED lamp designed as a direct replacement for CFLni |
|
| | IEC 62612:2013 or IEC 62612:2013+ AMD:2015 or IEC 62612:2013+ AMD1:2015+ AMD2:2018 |
The luminous flux measurement test must be conducted in accordance with CIE S 025:2015 |
| | | | IEC 62612:2013 or IEC 62612:2013+ AMD:2015 or IEC 62612:2013+ AMD1:2015+ AMD2:2018 |
The luminous flux measurement test must be conducted in accordance with CIE S 025:2015 |
| (d) | Refrigerator (other than a commercial storage refrigerator) |
|
| | | IEC 62552‑3:2015+ AMD1:2020 |
| (e) | Commercial storage refrigerator |
|
| | | | | | | The test must be conducted using dynamic broadcast content video signal |
| | (ii) | All (for standby power) |
|
| | | | | | Method 2‑1‑1B of IEC 60034‑2‑1:2014 or Method B of IEEE 112‑2004 |
| | | | IEC 62442‑1:2011 or IEC 62442:2018 |
| | | | |
|
| 1. Where the expression “for standby power” appears in relation to a regulated good, the applicable test standard or method corresponding to that regulated good applies in relation to that regulated good when it is in standby mode. |
| 2. Unless otherwise stated, the applicable test standard or method corresponding to a regulated good applies in relation to that regulated good when it is not in standby mode. |
|
”. |
|
|
|
|