1. These Regulations may be cited as the Fire Safety (Emergency Response Plan) Regulations.
[S 539/2013 wef 01/09/2013]
Definitions
2. In these Regulations, unless the context otherwise requires —
“Arson Prevention Plan”, in relation to any specified premises, means a plan which contains information on the preventive measures which are to be adopted in the specified premises to safeguard against arson and such other threats which could result in fire;
[S 539/2013 wef 01/09/2013]
“designated premises” means any premises or class of premises which are designated in the Fire Safety (Premises Requiring Emergency Response Plan) Notification 2013 (G.N. No. S 538/2013);
[S 539/2013 wef 01/09/2013]
“Emergency Response Plan”, in relation to any designated premises, means a plan which contains information on the types of fire safety measures that are provided for in the designated premises, and includes —
(a)
the floor layout plans of the building;
(b)
actions to take in the event of fire and related emergencies and evacuation procedures for the premises; and
(c)
in the case of specified premises, the Arson Prevention Plan for the building;
[S 539/2013 wef 01/09/2013]
“Fire Command Centre” means a room within any premises which is specifically designated for the purpose of command and control of operations in the event of fire or other emergencies and fitted with the necessary equipment;
“specified premises” means any premises or class of premises which are specified in the Fire Safety (Premises Requiring Fire Safety Manager and Company Emergency Response Team) Notification 2013 (G.N. No. S 537/2013).